CLIP SPORTS FLOOR
SPECIFIER'S AND INSTALLATION INSTRUCTIONS

D 2.1

 

D 2.1

 


1. SPECIFIER'S INFORMATION


INFORMATION 
CLIP SPORTS FLOOR SYSTEM

D 1.0 General information
Junckers Sports Floors
D 2.1 Specifier's and Installation
instructions

Table 1

1.1 SYSTEM SPECIFICATION

Floor construction
Junckers Clip Sports Floor System is based on 22 mm solid hardwood floorboards installed as a floating floor with steel clips on a 10 or 15 mm resilient foam underlay.

If you wish to install with starting point in the centre of the hall
Use Junckers Center-Row Board, which is constructed with a double clip-groove and a tongue on both sides. This enables installation in two directions. The board is available in 22 mm beech premium, silk-matt lacquered.

Construction height:
When using 10 mm SportsFoam: 32 mm.
When using 15 mm SportsFoam: 37 mm.

Performance:
The floor system is categorized as an area elastic sports floor with medium shock absorbency and elasticity particularly suitable for fitness and aerobics as well as in refurbishment projects.

The floor system is tested and approved according to:
- The European Sport Norm EN 14904 class A3, when using Junckers 10 mm SportsFoam
- FIBA level 2, when using Junckers 15 mm Sports Foam.

Step sound reduction by installation on heavy constructed horizontal divisions:
22 mm floorboards on 10 mm SportsFoam underlay: 18 dB.
22 mm floorboards on 15 mm SportsFoam underlay: 19 dB.

For general information about sound and practical guidelines on acoustics in floor constructions, see E 5.0.​

Read all information:
Please note that full documentation of a this floor system comprises General information and Specifier's and Installation instructions, see table 1.

1.2 FLOOR COMPONENTS  - CLIP SPORTS FLOOR SYSTEM

 

  1. Junckers 2-strip solid hardwood floorboards for sport
    Thickness x width x length
    22 x 129 x 3700 mm

    Wood Species, grade and surface:
    See data sheet B 2.0
  2. Steel Clips
  3. Intermediate layer
    10 or 15 mm Junckers SportsFoam
  4. Moisture barrier on concrete
    Junckers SylvaThene moisture barrier, 0.20 mm PE membrane,
    4 x 25 metre.
  5. Header joint adhesive
    Junckers SylvaFix
  6. Junckers Expansion strip
    Height x width x length
    12 x 12 x 1000 mm
  7. Expansion gap at the wall
    2 mm per metre of floor width on each side, min. 15 mm.
    Is also required at fixed points, e.g. columns.
  8. Junckers Combi sports skirting

Fig. 1


1.3 LOAD-BEARING STRENGTH OF THE SYSTEM

Load-bearing strength of the clip system depends on the type of load, see table 2.

See also data sheet D 1.0 - Stiffness and load-Bearing strength of floors.

Table 2 Loading types
Floorboard thickness Area load
per m²
Area load
ø25 mm
Area load
100x100 mm
Wheel
load
22 mm 800 kg 350 kg 400 kg See D 1.0
Table 1

1.4 CHOICE OF SUB FLOOR

Subfloors must be self-supporting and can be made of concrete, lightweight concrete, screed or in connection with renovation be an existing sports floor with e.g. a synthetic or wooden floor surface.

The elasticity of the subfloor has a direct impact on the properties of the completed floor in terms of deflection, impact absorption and ball bounce.

In renovation projects the elasticity and load bearing strength of the existing floor must be assessed in relation to the use of the floor.

If the floor area is made of several types of subfloors, it must be of uniform elasticity and flatness, to ensure a uniform performance of the sports floor.


1.5 BEFORE BEGINNING TO INSTALL THE FLOOR

The building must be weather tight. The heating system must be installed and tested, and during the heating season there should be a constant heat supply.

Cast concrete elements, including casting of sockets for fixtures and fittings, screeding and other wet trades which can contribute moisture to the building, e.g. priming of paintwork, must also be completed.

The relative humidity in the building must be within the relative humidity interval expected, when the building is in use and the room temperature approx. 20 °C.


Fig. 2

1.6 MOISTURE PROTECTION

Concrete subfloors
The residual moisture contained in the concrete or screed must not exceed 90 % RH.
(UK: Concrete moisture max. 75 % RH acc. to BS 8201, when checked by measurement).

At ground and upper levels protection against moisture both from within the building and from the ground is required.

A moisture barrier is established by laying Junckers SylvaThene moisture barrier directly on the concrete, see Fig. 2.

Fig. 3

Wooden subfloors
The moisture content of a wooden subfloor must be in balance with the relative humidity of the room, i.e. moisture content of 6-12%.

For renovation projects where floating floor systems are laid on existing wooden subfloors, it must be ensured that the entire structure has been designed to the correct specifications regarding moisture.

Usually, no additional moisture protection is laid on top of an existing wooden floor as this may course the risk of fungal attacks in the sub construction, see fig. 3.

Fig. 4

1.7 FLATNESS OF THE SUB FLOOR

The subfloor must be levelled so that any deviations in the flatness do not conflict with the requirements of the method stated below.

Straight edge:
The subfloor must be flat with a maximum deviation of 2 mm under a 1.5 m straight edge.
(UK: 3 mm under a 2 m straight edge).
(US: 3/16” under a 10 ft. straight edge).

Deviations are measured as gaps under the straight edge. The surface must be smooth. Any irregularities must be corrected by grinding or by using a self levelling compound.


1.8 INTERMEDIATE LAYER - SPORTSFOAM

As intermediate layer for a Junckers floating sports floor, use Junckers 10 or 15 mm SportsFoam. Type depends on needed performance.

For more information, see Junckers SportsFoam H 3.3.


1.9 EXPANSION STRIP AND ADHESIVE

Junckers Expansion strip must be mounted tautly between all floorboard ends and walls.

All floorboard header joints must be glued with Junckers SylvaFix, header joint adhesive. Never apply adhesive to the longitudinal sides of the floorboards, except for the floorboards in the last row, if the clip-groove is cut off.


Fig. 5

1.10 CHOICE OF INSTALLATION CLIP

Installation Clips are available in different sizes according to various air humidity ranges.

The clip size is selected primarily on the basis of the expected maximum relative humidity (RH) in the building during the year, see fig. 5.

However, in order to minimize the overall movements of larger floor areas, it may be necessary to choose a larger clip size than normally corresponding to the expected maximum RH. 

The general rule for sports floors is as stated in table 3:

Table 3      

Floor area

Clip size

Humidity range %

Gaps at installation time

Label colour/Clip taging

< 500 m²

129.4 mm

35 - 65

Appr. 0.4 mm

Yellow, 2-hole

> 500 m²

129.6 mm

35 - 65

Appr. 0.6 mm

Black, 2 ½-hole

We ask you to contact Junckers for advice, if the expected humidity range does not match the range 35 - 65 %.

We have clips matching any humidity range, see examples in table 4 below.

Table 4    

Clip size

Humidity range %

Gaps at installation time

Label colour/Clip taging

128.8 mm

10 - 40 **

Arctic/desert areas*

White, 0-holes

129.1 mm

25 - 55 **

Appr. 0.1 mm

Green, 1-hole

129.8 mm

65 - 85

Appr. 0.8 mm

Red, 3-holes

130.2 mm

75 - 95

Appr. 1.2 mm

Orange, 4-holes

*Arctic/desert areas
The 128.8 mm clip is used in arctic and desert areas. Acclimating of the wood prior to installation is necessary.

** Humidity range from 10 - 55 %
In a very dry environment there will be some larger permanent gaps between the floorboards.

Specifiers are advised to contact Junckers Technical department if such conditions are anticipated.

Fluctuation in the relative humidity
With all clip sizes, gaps will appear when the relative humidity falls to, or below, the lower end of the recommended humidity range.


1.11 NET CONSUMPTION OF MATERIALS

Floorboards: Area + approx. 2 % wastage
CenterRow-Board*: Number of boards corresponding to the length of the floor. Supplied in packs of 4 pcs. x 3700 mm.
Steel Clips**: 17 pcs. per m²
Junckers SportsFoam, 10 or 15 mm: Area + approx. 2 % wastage
Junckers SylvaFix, Header joint Adhesive: 1 bottle per 75 m²
Junckers Expansion strip: 2 x floor width
Junckers SylvaThene moisture barrier (always on concrete): Area + approx. 10 % wastage incl. overlaps

* When installation is started in the centre of the hall. Available in 22 mm beech premium, silk-matt lacquered.
** For halls with many columns, etc. extra clip consumption must be included in the estimated consumption.

2. INSTALLATION INSTRUCTIONS


2.1 WHEN TO START INSTALLATION

Solid hardwood floorboards should always be laid immediately after arrival at the building. The plastic wrap must not be removed until installing of the floor begins.


2.2 MOISTURE BARRIER

A moisture barrier of min. 0.20 mm PE membrane is laid, e.g. Junckers SylvaThene moisture barrier. Ensure an overlap of 200 mm at all joints, continuing up walls, etc.

The moisture barrier must to be taped at all lap joints using a tape 50 mm vide.


2.3 INTERMEDIATE LAYER - SPORTS FOAM

Junckers SportsFoam is laid parallel to the laying direction of the floorboards with joints fully closed and taped in place.


2.4 CENTER-ROW BOARD

By installation with starting point in the centre of the hall, laying is started with a Center-Row board.

The floorboard is constructed with a double clip-groove and a tongue on both sides.

The CenterRow board is placed in the entire length of the hall and hereafter, installation can continue in two directions.

2.5 CLIPS, EXPANSION STRIP AND ADHESIVE

Before starting to install the floorboards, make sure that the clip size corresponds to the expected relative humidity in the building during a full year.

With the underside of the floorboard facing upwards the clip-end with hole(s) is knocked down into the clip groove, so that the free end of the clip points in the direction of the tongue, which is also the laying direction, see fig. 4.1 & 4.2.

All floorboard header joints are carefully glued, see fig. 4.3. Use enough glue to secure a tight and strong joint. Never apply adhesive to the longitudinal sides of the floorboards, except for the floorboards in the last row, if the clip-groove is cut off.

Junckers expansion strip (A) is mounted tautly between floorboard ends and walls, see fig. 4.4.


2.6 MOUNT THE CLIPS CORRECT

The first and last clips are placed maximum 80 mm / 3" from the floorboard end adjoining the end wall.

The spacing of the clips must be maximum 500 mm / 20".

Ensure that the clips do not touch each other by alternating them (in line) at approx. 50 mm / 2" intervals.

Make sure the free end of the clips is properly placed in the groove on the neighboring floorboard.

Since this can be difficult due to the elasticity of the mat, use e.g. a small metal plate or the like as a load spread sheet. The metal plate is moved as work progresses.


2.7 DISTANCE TO WALLS AND FIXED INSTALLATIONS

The distance (A) between the floorboards and walls/vertical fixed installations is calculated as 2 mm per running metre of floor width on each side. 

(B): Expansion strip.

2.8 PATTERN, FLOORBOARD JOINTS AND LAST ROW

Lay the floorboards in an irregular pattern, spacing floorboard joints as evenly as possible. The distance (A) between floorboard joints in two consecutive rows should be at least 450 mm / 18", see fig. 7.1.

Stave joints in one row may not adjoin stave joints in the adjacent row, but must be spread as widely as possible and minimum 50 mm / 2".

Adjust the floorboards in the last row. Remember the correct expansion gap (B) to the wall, see fig. 7.2. The last row of floorboards is glued in the groove, if the clip-groove is cut off and is laid against the floorboards in the previous row. Use a joint puller (C) to knock the last floorboard into place, see fig. 7.3. 

Remember to remove spacing blocks before skirting is mounted.


2.9 BUSHINGS

When mounting of bushings in the floor the internal diameter of the bushing must exceed that of the pipe, i.e. the external diameter of the net pole, by at least 40mm.

At the outermost zones of the floor all bushings are mounted eccentrically towards the middle of the floor in relation to the sockets in the concrete, see drawing.

Floor rosettes must be mounted to allow both vertical and horizontal movement of the floor to take place unimpeded.


2.10 COMBI SPORTS SKIRTING

Depending on the wanted cover width, the skirting can be mounted upright or in a lying position, see drawing.

The foot of the skirting must lie flat and be in contact with the floor. End joints may be either butt jointed together or cut as a 450 mitre joint to enhance the visual effect of the joint.

The skirting can be either glue fixed to the walls or screw fixed.

Do not fix the skirting to the Junckers floor and ensure that the skirting is not exerting any downward pressure on the floor.